CO Controller

Product description


Product Description





CO Controller

CO Controller/Meter especial design for parking lot

 

CO Controller/Meter  Features 

 

Design for real-time detection air carbon monoxide.

High accuracy humidity and temperature detection optional

LCD display carbon monoxide and optional temperature & RH measurement.

Smart buttons for easy operation

Carbon monoxide

detector/controller

Excellent electrochemical CO sensor with more than 5 years lift time

Replaceable CO sensor

u   Provide 1X analog linear output (0~10VDC/4~20mA selectable)

for the measurement

Providing up to two dry contact outputs with presetting the setpoint

Modbus RS485 communication interface optional

Provide two easy methods for calibration and setup alarm points by end users: infrared remote controller or a software via RS485

 

24VAC/VDC power supply

Carbon monoxide

Transmitter

(only for the unit with one analog output)

CE-Approval

 Typical Applications

 

In office and residence areas to detect CO2 level

 

In undergroung parking lots and garages

 

In BAS to detect the CO2 and the data transmittance

 

For greenhouse and plant bin

 

For ventilation control system

 Specifications

 

Sensors

Gas Sensor

Electrochemical carbon monoxide sensor

Sensor lifetime

Normally more than 3 years, replaceable

Warm up time

1hour (first time)  

Response Time

Within 60 seconds

Signal Update

1s

CO Measuring Range

0~500ppm(default)/0~100ppm/0~1000ppm selectable

Accuracy

<1ppm+5%reading

Stability

±5% (over 900 days)

Temperature & Humidity Sensor (optional)

Temperature

Relative Humidity

Sensing element:

Band-gap-senor

Capacitive humidity sensor

Measuring range

-20°C~60°C

0 -100%RH

Accuracy

±0.5°C (20~40°C)

±4.0%RH (25°C, 15%-85%RH)

Display resolution

0.1°C

0.1%RH

Stability

±0.1°Cper year

±1%RH per year

Outputs

LCD Display (optional)

Display COmeasurement

or CO+ temperature& humidity measurements

Analog Output

1X0~10VDC or 4~20mA linear output

Analog Output Resolution

16Bit

Relay dry contact Output

Up to two dry-contact outputs

Max, switching current 3A (230VAC/30VDC), resistance Load

Modbus Interface

Modbus RS-485 with 19200bps(default), other rates selectable

in the order. 15KV antistatic protection

Electrical and General Items

Power Supply

24VAC/VDC              

Power Consumption

2.8W

Wiring Standard

Wire section area<1.5mm2

Working Condition

-10°C~60°C(14~140°F); 5~99%RH, non condensing

Storage Conditions

-10~60°C(14~140°F)/ 5~99%RH, non condensing

Net Weight

260g    

Manufacturing Process

ISO 9001 Certified

Housing and IP class

PC/ABS fireproof plastic material, protection class: IP30