CO detector
Product description
Gas detected | Carbon monoxide |
Sensing element | Semiconductor carbon monoxide gas sensor |
Power Supply | 24VAC/VDC |
Consumption | 2.5 W |
Warm up time | 36 hours (first time) 10 minutes (operational) |
Response Time | <5 minutes for 90% step change |
Signal Update | 1s |
CO Measuring Range | 0~500ppm |
Six indicator lights | The first green indicator light: CO≤0ppm The first and the second green indicator lights: CO ≥20ppm The first orange indicator light: CO≥50ppm The first and the second orange indicator lights: CO ≥100ppm The first red indicator light: CO≥200ppm The first and the second red indicator lights: CO≥300ppm |
Relay output | One dry contact output, rated switching current 2A (resistant load) |
Communication rate | RS485, 19200bps rate, 15KV antistatic protection |
Operation temperature | 0~60°C(32~140°F) |
Operation humidity | 5~95%RH, non condensing |
Storage conditions | -10~60°C(14~140°F) |
Net Weight | 195g |
Dimensions | 100mm×80mm×28mm |
Installation standard | 65mm×65mm or 2”×4” junking box |
Wiring terminals (max.) | 6 |
Housing and IP class | PC/ABS fireproof plastic material, protection class: IP30 |
Features:
1) Wall mounting, real time detect CO level with measuring range of 0~500ppm.
2) Japanese semiconductor CO gas sensor is inside with normal 5 years lifetime.
3) Full time detects the ambiance carbon monoxide with six indicator lights indicating six different CO ranges
4) One on/off output optional for control a fan or an alarm device.
5) Convenient to select the CO range to control the relay output during four carbon monoxide ranges via a set of jumpers so that
6) RS-485 communication interface optional with 15KV antistatic protection
Recommended products